LRGBJ - ZHD Series Current Transformers
40.5 to 252 kV
5 to 5000 A (8000 A on specific configurations)
Dealing with very high currents involves a slightly different approach. The LRGBJ-ZHD Current Transformer's design has been further developed to process routine currents as high as 5000 A. On specific configurations this design can accommodate 8000 A
The ZHD series is actually a "2-CT-in-one" design. The top of the device is accepting the high current line, providing a transformation ratio of K1. The bottom of the product is a high voltage CT with a transformation ratio of K2 using the secondary current generated through K1. The final ratio of this Current Transformer is then K=K1*K2
This unique design allows a remarkable flexibility in dealing with very high currents.
Specifications and Performance
- Rated primary voltage: 40.5 - 252 kV
 - Rated primary current: >2500 A to 5000 A (up to 8000 A under specific conditions - please contact us)
 - Rated secondary current: 5A, 1A
 - Rated output 10-50VA
 - Metering accuracy class: 0.2S, 0.2, 0.5S and 0.5 class
 - Accuracy limit factor 5, 10, 15, 20, 30, 40
 - Protection accuracy class: 5P, 10P and TPY (additional classes on demand)
 - Secondary cores: 1-8
 
LRGBJ Series Current Transformers
| Accuracy Class | 0.2S, 0.2, 0.5S, 0.5 or 5P, 10P, TPY (for other classes, please contact us) | 
| Rated Current | > 2500 A to 5000 A (up to 8000 A under specific conditions) | 
| Ambient Temperature  | +45 ° C (113 ° F) to –50 ° C (-58 ° F) | 
| Insulation Level (kV)  | 252 kV rated: 460/1050/1200  126 kV rated: 230/550/630  | 
| Level Partial Discharge | <5 pC | 
Standards
All products comply with IEC-61869-2 "Current Transformers" and IEEE C57.13 standards Protective class current transformers comply with IEC-44-6:"Requirements for Protective Current Transformers for Transient Performance"
Maintenance
No maintenance is needed on our Current Transformers
Option: A simple monitoring feature of tanδ is proposed as an option for yearly monitoring of equipment.
Reminder: for electrical safety reasons, secondary circuits should not be opened during operation of any Current Transformer.
Inquiry Check List
When placing an order, customer's specification needs to include:
| Reference Standard | 
| Rated voltage | 
| Rated current | 
| Rated frequency | 
| Rated transformation ratio | 
| Number of secondary windings | 
| Rated output | 
| Accuracy class(es) | 
| Accuracy limit factor | 
| Instrument security factor | 
| Environmental Conditions (Altitude, Pollution Class)  | 
If users have specific requirements, custom designs are available upon request.
Dimensions
LRGBJ-ZHD Series
| Model Reference | Rated Voltage (kV)  | Rated Current (A)  | L (mm)  | W (mm)  | D (mm)  | Creepage Distance (mm)  | Weight (kg/lb)  | 
| LRGBJ - ZHD - 252 / 6000 | 252 | 5000~6000 | 2950 | 1520 | 855 | 3200 | 650/1433 | 
| LRGBJ - ZHD - 126 / 6000 | 126 | 5000~6000 | 1900 | 750 | 385 | 6300 | 1200/2646 | 
| LRGBJ - ZHD - 72 / 6000 | 72 | 5000~6000 | 1550 | 750 | 385 | 1925 | 400/882 | 
| LRGBJ - ZHD - 40.5 / 6000 | 40.5 | 5000~6000 | 1150 | 750 | 385 | 1015 | 200/441 | 